Home

>

LV AL/PVC/PVC Power Cable

LV AL/PVC/PVC Power Cable


Standard and Approval:IEC 60502 or equivalent
Conductor:Solid or stranded,AL conductor,to IEC 60228 class. 1 or class. 2
Insulation:PVC
Sheath:PVC
U0/U:600/1000V
Test voltage:3.5KV/5 min
Max. temperature:70

Description

0.6/1KV Low voltage AL Conductor PVC Insulation PVC Sheath Power Cable
IEC 60502-1 Standard or equivalent

These cables are designed for low-voltage power distribution systems. They are suitable for both indoor and outdoor installations, including cable ducts, underground conduits, power substations, and industrial settings where there is no risk of physical damage.

Specification

Size Insulation Thickness (mm) Approx.OD (mm) Max. Resistance @20 degree (Ohm/Km)
1x35 1.2 11.9 0.868
1x50 1.4 13.4 0.641
1x70 1.4 15.3 0.443
1x95 1.6 17.2 0.32
1x120 1.6 18.7 0.253
1x150 1.8 20.8 0.206
1x185 2 22.9 0.164
1x240 2.2 25.7 0.125
1x300 2.4 28.3 0.1
1x400 2.6 31.9 0.0778
2x25 1.2 19.8 1.2
2x35 1.2 22.0 0.868
2x50 1.4 25.0 0.641
2x70 1.4 28.8 0.443
2x95 1.6 32.6 0.32
2x120 1.6 35.8 0.253
2x150 1.8 39.8 0.206
2x185 2 44.2 0.164
2x240 2.2 49.8 0.125
2x300 2.4 55.0 0.1
2x400 2.6 62.2 0.0778
3x25 1.2 21.1 1.2
3x35 1.2 23.4 0.868
3x50 1.4 26.7 0.641
3x70 1.4 31.0 0.443
3x95 1.6 34.9 0.32
3x120 1.6 38.3 0.253
3x150 1.8 42.8 0.206
3x185 2 47.5 0.164
3x240 2.2 53.5 0.125
3x300 2.4 59.1 0.1
3x400 2.6 67.1 0.0778
4x25 1.2 23.1 1.2
4x35 1.2 25.8 0.868
4x50 1.4 29.6 0.641
4x70 1.4 34.4 0.443
4x95 1.6 38.7 0.32
4x120 1.6 42.8 0.253
4x150 1.8 47.6 0.206
4x185 2 53.1 0.164
4x240 2.2 59.7 0.125
4x300 2.4 66.0 0.1
4x400 2.6 74.8 0.0778
... ... ... Contact us for more details

Size

Get in Touch

*We respect your confidentiality and all information are protected.